Class A Protection:
It initiates a main CB trip as fast
as can be arranged. Electrical failure damage propagates so quickly that class A
tripping is essential. Taking the trip relay and CB operating time into
account, this means about 120 ms (6 cycles) after initiation. With most modern
CBs this time may be reduced to about 80 ms. The following situations are
commonly protected by class A trip through unit lock out relays 86G-1 and
86G-2(Instantaneous Tripping of unit).
A.
Tripping conditions for 86G-1 will
energize on the operation of the following protections :
1.
Differential protection of Generator
Transformer and Unit Auxiliary transformers-A/B.
2.
Generator and Transformer overall
differential protection.
3.
Generator transformer and UAT fire
protection.
4.
Generator inter winding protection.
5.
Generator Transformer over flux
protection.
6.
Bus bar protection of switchyard and
breaker back up protection.
7.
Generator pole slipping.
8.
Generator main earth fault (64G-1).
9.
Generator second rotor earth fault.
10.
Low forward power relay when ESV and IV are
closed.
B.
Tripping of 86G-1 will result in
following operations:
1.
Tripping of UAT-A & B breakers of
6.6 KV side.
2.
Opening of Generator main CB.
3.
Opening of transfer bus breaker(if unit
is running on transfer bus)
4.
Opening of sequential isolators.
5.
Tripping of turbine lock out relay.
6.
Tripping of master fuel trip relay.
C.
Tripping of unit lock out relays 86G-2
will energise on the operation of following protection :
1.
Generator stands by earth fault
protection.
2.
Generator transformer (HV Side) –
restricted earth fault protection.
3.
Buchholz relay operation of generator
transformer or UAT-A/B.
4.
Generator transformer pressure relief
valve operation.
5.
Excitation system trouble-over current,
loss of thyristors and over voltage.
6.
Operation of 86G-1.
7.
Any of HP heaters level high (4250 mm)
8.
Turbine in trouble-high axial shift
(-1.7 mm, +1.2 mm), very low vacuum (540mmHg), or very low lubricating oil
pressure (0.3 kg/cm2).
D.
Tripping of 86G-2 will result in
following operations :-
1 to 6 operations are same as those
of B.
7.
Tripping of field breaker.
8.
Tripping of unit lock out relay 86G-4
E.
Tripping of 86G-1 and 86G-2 energise
86G-4 which in turn will affect the
following operations :
1.
Tripping of following auxiliaries:-
. CW
pumps A and C.
.
Condensate pumps A and B.
.
Boiler feed pumps A,B and C.
. PA
Fan A and B.
. FD
Fan A.
2.
Auto closing of 6.6KV tie
breaker to unit buses from the 6.6KV station buses.
3.
AVR mode changes over from Auto
to Manual.
4.
Stops the generator transformer
cooler pumps and fans.
The maximum arresting force probably won’t play into your planning very much. When worn with a body harness, both of these classes meet the OSHA requirement of limiting the arresting force on the human body to 1800 lbs.
ReplyDeleteTransformer Manufacturer in India