Skip to main content

Generator Protection - Class-A Protection

Class A Protection:
It initiates a main CB trip as fast as can be arranged. Electrical failure damage propagates so quickly that class A tripping is essential. Taking the trip relay and CB operating time into account, this means about 120 ms (6 cycles) after initiation. With most modern CBs this time may be reduced to about 80 ms. The following situations are commonly protected by class A trip through unit lock out relays 86G-1 and 86G-2(Instantaneous Tripping of unit).



A.
Tripping conditions for 86G-1 will energize on the operation of the following protections :

1.                 
Differential protection of Generator Transformer and Unit Auxiliary transformers-A/B.

2.                  
Generator and Transformer overall differential protection.

3.                  
Generator transformer and UAT fire protection.

4.                 
Generator inter winding protection.

5.                  
Generator Transformer over flux protection.

6.                  
Bus bar protection of switchyard and breaker back up protection.

7.                  
Generator pole slipping.

8.                 
Generator main earth fault (64G-1).

9.                  
Generator second rotor earth fault.

10.              
Low forward power relay when ESV and IV are closed.

B.                
Tripping of 86G-1 will result in following operations:

1.                 
Tripping of UAT-A & B breakers of 6.6 KV side.

2.                  
Opening of Generator main CB.

3.                 
Opening of transfer bus breaker(if unit is running on transfer bus)

4.                  
Opening of sequential isolators.

5.                  
Tripping of turbine lock out relay.

6.                  
Tripping of master fuel trip relay.

C.                 
Tripping of unit lock out relays 86G-2 will energise on the operation of following protection :

1.                 
Generator stands by earth fault protection.

2.                  
Generator transformer (HV Side) – restricted earth fault protection.

3.                  
Buchholz relay operation of generator transformer or UAT-A/B.

4.                 
Generator transformer pressure relief valve operation.

5.                  
Excitation system trouble-over current, loss of thyristors and over voltage.

6.                  
Operation of 86G-1.

7.                  
Any of HP heaters level high (4250 mm)

8.                 
Turbine in trouble-high axial shift (-1.7 mm, +1.2 mm), very low vacuum (540mmHg), or very low lubricating oil pressure (0.3 kg/cm2).

D.                
Tripping of 86G-2 will result in following operations :-

1 to 6 operations are same as those of B.

7.                  
Tripping of field breaker.

8.                  
Tripping of unit lock out relay 86G-4

E.                 
Tripping of 86G-1 and 86G-2 energise 86G-4 which in turn will affect the  following operations :

1. 
Tripping of following auxiliaries:-
 .  CW pumps A and C.
 .  Condensate pumps A and B.
 .  Boiler feed pumps A,B and C.
 .  PA Fan A and B.
 .  FD Fan A.

2. 
Auto closing of 6.6KV tie breaker to unit buses from the 6.6KV station buses.

3. 
AVR mode changes over from Auto to Manual.

4. 
Stops the generator transformer cooler pumps and fans.

Comments

  1. The maximum arresting force probably won’t play into your planning very much. When worn with a body harness, both of these classes meet the OSHA requirement of limiting the arresting force on the human body to 1800 lbs.
    Transformer Manufacturer in India

    ReplyDelete

Post a Comment

Popular posts from this blog

One & Half Breaker Arrangement - Substation design (Bus Bar Schemes)

In this scheme, three circuit breakers are used for controlling two circuits which are  connected between two bus bars. Normally, both the bus bars are in service. A fault on any one of the bus bars is cleared by opening of the associated circuit breakers  connected to the faulty bus bar without affecting continuity of supply. Similarly, any circuit  breaker can be taken out for maintenance without causing interruption. Load transfer is  achieved through the breakers and, therefore, the operation is simple. However, protective  relaying is somewhat more involved as the central (tie) breaker has to be responsive to  troubles on either feeder in the correct sequence. Besides, each element of the bay has to be  rated for carrying the currents of two feeders to meet the requirement of various switching  operations which increases the cost. The breaker and a half scheme is best for those  substations which handle large quantities of power and where the orientation of out g

Generator Protection - Rotor Earth Fault Protection (64R1/ 64R2)

Rotor Earth Fault Protection (64R1/64R2) The field circuit of generator (i.e. rotor winding) is an isolated D.C. circuit and not earthed anywhere. The field can be exposed to abnormal mechanical or thermal stresses due to vibration, excessive currents or choked cooling medium flow. This may result in a breakdown of the insulation between the field winding and the rotor iron at one point where the stress has been too high. A single earth fault in the field winding or its associated circuits, therefore, gives rise to a negligible fault current and does not represent any immediate danger. If however a second ground fault should occur, heavy fault current and severe mechanical unbalance may quickly arise and lead to serious damage. It is essential therefore that any occurrence of insulation failure is discover and that the machine is taken out of service as soon as possible. Normally the machine is tripped instantly on occurrence of second rotor earth fault. Three method are avai

Generator Protection - Stator Earth Fault Protection

Stator Earth Fault Protection In most countries, it is a common  practice  to ground the generator neutral through a Grounding Transformer having a loading resistor across its secondary. This method of earthing is called high impedance earthing where the earth fault current is limited to 5-10 Amps. Tuned reactors which limit the ground fault current to less than 1.0 A are also used. The generator grounding resistor normally limits the neutral voltage transmitted from the high voltage side of the unit transformer in case of a ground fault on the H.V. side to maximum 2-3% of rated generator phase voltage. Short circuits between the stator winding in the slots and the stator core are the most common electrical fault in generators. Interturn faults, which normally are difficult to detect, will quickly develop into a ground fault and will be tripped by the stator ground fault protection. 95% stator ground fault relay for generator For generators with unit transformer