Skip to main content

Generator Protection - Stator Earth Fault Protection

Stator Earth Fault Protection

In most countries, it is a common practice to ground the generator neutral through a Grounding Transformer having a loading resistor across its secondary. This method of earthing is called high impedance earthing where the earth fault current is limited to 5-10 Amps. Tuned reactors which limit the ground fault current to less than 1.0 A are also used.

The generator grounding resistor normally limits the neutral voltage transmitted from the high voltage side of the unit transformer in case of a ground fault on the H.V. side to maximum 2-3% of rated generator phase voltage.


Short circuits between the stator winding in the slots and the stator core are the most common electrical fault in generators. Interturn faults, which normally are difficult to detect, will quickly develop into a ground fault and will be tripped by the stator ground fault protection.

95% stator ground fault relay for generator

For generators with unit transformer and with high impedance grounding of the neutral, a neutral voltage relay with harmonic immunity and independent time delay is used. The relay is normally set to operate at 5% of maximum neutral voltage with a time delay of 0.3-0.5 second. With this voltage setting, it protects approximately 95% of the stator winding.

It also covers the generator bus, the low voltage winding of the unit transformer and the high voltage winding of the unit aux. transformer.

Relay details: 64 A/B- Neutral displacement relay having IDMT or definite time characteristic.



95% Stator Ground Fault Protection


100% stator ground fault relay for generator

Ground fault caused by mechanical damage may occur close to the generator neutral. Today there is a distinct trend towards providing ground fault protection for the entire stator winding (100% ground fault protection).

The principle diagram of the relay is shown in Fig. The 100% stator ground fault scheme includes a 95% unit-I, which covers the stator winding from 5% of the neutral and a 3rd harmonic voltage measuring unit -II which protects the rest of the stator winding.

For generators with 3rd harmonic voltage less than 1%, a filter is available with a damping factor of more than 100.

When the generator is running and there is no ground fault near the neutral, the 3rd harmonic voltage unit-II and the voltage check unit-IV are both activated and the relay contact used in alarm/trip circuit is open. If a ground fault occurs close to the generator neutral, the 3rd harmonic voltage unit will reset, operating relay contact will close and alarm or tripping is obtained.

The voltage check is included to prevent faulty operation of the relay at generator standstill or during the machine running up or running down period.

Generator which produces more than 1% 3rd harmonic voltage under all service conditions can have the entire stator winding up to and including the neutral point protected by the 100% stator ground fault relay.


   
100% Stator Ground Fault Protection

Comments

Post a Comment

Popular posts from this blog

One & Half Breaker Arrangement - Substation design (Bus Bar Schemes)

In this scheme, three circuit breakers are used for controlling two circuits which are  connected between two bus bars. Normally, both the bus bars are in service. A fault on any one of the bus bars is cleared by opening of the associated circuit breakers  connected to the faulty bus bar without affecting continuity of supply. Similarly, any circuit  breaker can be taken out for maintenance without causing interruption. Load transfer is  achieved through the breakers and, therefore, the operation is simple. However, protective  relaying is somewhat more involved as the central (tie) breaker has to be responsive to  troubles on either feeder in the correct sequence. Besides, each element of the bay has to be  rated for carrying the currents of two feeders to meet the requirement of various switching  operations which increases the cost. The breaker and a half scheme is best for those  substations which handle large quantities of power and where the orientation of out g

Generator Protection - Rotor Earth Fault Protection (64R1/ 64R2)

Rotor Earth Fault Protection (64R1/64R2) The field circuit of generator (i.e. rotor winding) is an isolated D.C. circuit and not earthed anywhere. The field can be exposed to abnormal mechanical or thermal stresses due to vibration, excessive currents or choked cooling medium flow. This may result in a breakdown of the insulation between the field winding and the rotor iron at one point where the stress has been too high. A single earth fault in the field winding or its associated circuits, therefore, gives rise to a negligible fault current and does not represent any immediate danger. If however a second ground fault should occur, heavy fault current and severe mechanical unbalance may quickly arise and lead to serious damage. It is essential therefore that any occurrence of insulation failure is discover and that the machine is taken out of service as soon as possible. Normally the machine is tripped instantly on occurrence of second rotor earth fault. Three method are avai