Stator Earth Fault Protection
In most countries, it is a common practice to ground the generator neutral through a Grounding Transformer having
a loading resistor across its secondary. This method of earthing is called high
impedance earthing where the earth fault current is limited to 5-10 Amps. Tuned
reactors which limit the ground fault current to less than 1.0 A are also used.
The generator grounding resistor
normally limits the neutral voltage transmitted from the high voltage side of
the unit transformer in case of a ground fault on the H.V. side to maximum 2-3%
of rated generator phase voltage.
Short circuits between the stator
winding in the slots and the stator core are the most common electrical fault
in generators. Interturn faults, which normally are difficult to detect, will
quickly develop into a ground fault and will be tripped by the stator ground
fault protection.
95% stator ground fault relay for
generator
For generators with unit
transformer and with high impedance grounding of the neutral, a neutral voltage
relay with harmonic immunity and independent time delay is used. The relay is
normally set to operate at 5% of maximum neutral voltage with a time delay of 0.3-0.5 second. With this voltage
setting, it protects approximately 95% of the stator winding.
It also covers the generator bus,
the low voltage winding of the unit transformer and the high voltage winding of
the unit aux. transformer.
Relay details: 64 A/B- Neutral
displacement relay having IDMT or definite time characteristic.
95% Stator
Ground Fault Protection
100% stator ground fault relay for generator
Ground fault caused by mechanical
damage may occur close to the generator neutral. Today there is a distinct
trend towards providing ground fault protection for the entire stator winding
(100% ground fault protection).
The principle diagram of the relay
is shown in Fig. The 100% stator ground fault scheme includes a 95%
unit-I, which covers the stator winding from 5% of the neutral and a 3rd
harmonic voltage measuring unit -II which protects the rest of the stator
winding.
For generators with 3rd harmonic
voltage less than 1%, a filter is available with a damping factor of more than
100.
When the generator is running and
there is no ground fault near the neutral, the 3rd harmonic voltage unit-II and
the voltage check unit-IV are both activated and the relay contact used in
alarm/trip circuit is open. If a ground fault occurs close to the generator
neutral, the 3rd harmonic voltage unit will reset, operating relay contact will
close and alarm or tripping is obtained.
The voltage check is included to
prevent faulty operation of the relay at generator standstill or during the
machine running up or running down period.
Generator which produces more than
1% 3rd harmonic voltage under all service conditions can have the entire stator
winding up to and including the neutral point protected by the 100% stator
ground fault relay.
100% Stator
Ground Fault Protection