Rotor Earth Fault
Protection (64R1/64R2)
The field circuit of generator
(i.e. rotor winding) is an isolated D.C. circuit and not earthed anywhere. The
field can be exposed to abnormal mechanical or thermal stresses due to
vibration, excessive currents or choked cooling medium flow. This may result in
a breakdown of the insulation between the field winding and the rotor iron at
one point where the stress has been too high.
A single earth fault in the field
winding or its associated circuits, therefore, gives rise to a negligible fault
current and does not represent any immediate danger. If however a second ground
fault should occur, heavy fault current and severe mechanical unbalance may
quickly arise and lead to serious damage. It is essential therefore that any
occurrence of insulation failure is discover and that the machine is taken out
of service as soon as possible. Normally the machine is tripped instantly on
occurrence of second rotor earth fault. Three method are available to detect
this type of fault.
First Rotor Earth Fault Protection
64 R1
Ø Potentiometer
method
Ø A.C.
injection method
Ø D.C.
injection method
POTENTIOMETER METHOD
In this scheme, a centre tapped
resistor is connected in parallel with the main field winding as shown in Fig. C.
The centre point of the resistor is connected to earth through a voltage relay.
An earth fault on the field winding will produce a voltage across the relay.
The maximum voltage occurring for faults at the ends of the winding.
A ‘blind spot’ exists at the centre
of the field winding, this point being at a potential equal to that of the
tapping point on the potentiometer. To avoid a fault at this location remaining
undetected, the tapping point on the potentiometer is varied by a push button
or switch. It is essential that station instructions be issued to make certain
that the blind spot is checked at least once per shift. The scheme is simple in
that no auxiliary supply is needed. A relay with a setting 5% of the exciter
voltage is adequate. The potentiometer will dissipate about 60 volts.
Fig C:
Potentiometer Method
A.C. INJECTION METHOD
This scheme is shown in Fig. D, it comprises of an
auxiliary supply transformer, the secondary of which is connected between earth
and one side of the field circuit through an interposed capacitor and a relay
coil.
The field circuit is subjected to an alternating
potential at the same level throughout, so that an earth fault anywhere in the
field system will give rise to a current which is detected by the relay. The
capacitor limits the magnitude of the current and blocks the normal field
voltage, preventing the discharge of a large direct current through the
transformer.
This scheme has an advantage over the
potentiometer method in that there is no blind spot in the supervision of the
field system. It has the disadvantage that some current will flow to earth
continuously through the capacitance of the field winding. This current may
flow through the machine bearings, causing erosion of the bearing surface. It
is a common practise to insulate the bearings and to provide an earthing brush
for the shaft, and if this is done the capacitance current would be harmless.
Fig D: A.C
Injection Method
D.C. INJECTION METHOD
The capacitance current objection
to the a.c. injection scheme is overcome by rectifying the injection voltage as
shown in Fig. E. The d.c. output of a transformer rectifier power unit is
arranged to bias the positive side of the field circuit to a negative voltage
relative to earth. The negative side of the field system is at a greater
negative voltage to earth, so an earth fault at any point in the field winding
will cause current to flow through the power unit. The current is limited by
including a high resistance in the circuit and a sensitive relay is used to
detect the current.
The fault current varies with fault
position, but this is not detrimental
Provide the relay can detect the
minimum fault current and withstand the maximum.
The relay must have enough
resistance to limit the fault current to a harmless value and be sufficiently
sensitive to respond to a fault which at the low injection voltage may have a
fairly high resistance.
Insulation leakage current, taking
into account of the high voltage to earth at the negative end of the winding
and any over voltage due to field forcing and so on.
Fig E: D.C.
Injection Method
2ND ROTOR EARTH FAULT PROTECTION (64R2)
In this test system is replaced by a
replica field system in the form of potential divider , two work 1 K
potentiometer in parallel with station D.C. is used so in fig.(F) SW1 at 1st
rotor E / F position. Closed switch S1 check that 1st rotor E/F relay VAEM
(64R1) operated. Shift S1 to balance. Obtain balance on the mA meter
(Galvanometer) by coarse / fine adjustment of potentiometer. Shift SW1 on test
position check operation of relay 64R2 by closing switch S2 thus creating an
unbalance which simulates second E/F.
ROTOR EARTH FAULT
The scheme to detect rotor earth in
case of brushless excitation system is show in fig.(G) in this case, rotor
earth fault relay forms the three arms of a bridge whose forth arm is the field
winding capacitance to rotor body. During rotor earth fault, this capacitance
gets shorted and the bridge becomes unbalanced operating the relay. Main
exciter winding, rotating diodes and generator field winding is protected by
this relay.
Fig G: Rotor Earth Fault
Pretty nice article! It was very helpful to me.
ReplyDelete