Class-B Protection:
It initiates the closing of turbine
stop and interceptor valve. The load reduces to 1% or less within a few
seconds; this situation is detected by a: Low Forward Power” relay which, after
a short delay, initiates a main CB trip. The process takes 4 to 5 sec from the
original initiation and is intended to prevent a possible speed run away if
over speed governor does not function correctly (Tripping of unit after a time
delay).
A.
Class B trip through unit lock out relay
86G-3 under following conditions
1.
Distillate flow to generator stator winding
decreases to 13 tons/hour.
2.
Distillate specific resistance is very
low (50K-ohms-cm).
3.
Generator transformer winding
temperature increases to 1250 C.
4.
UAT A&B winding temperature
increases to 1250 C.
5.
Generator transformer back up over
current and earth fault protection.
6.
Generators overload protection.
7.
Generator loss of excitation protection.
8.
Generator negative phase sequence
protection.
9.
Generator back up distance protection.
10.
GT/UAT A & B phase over current
protection.
11.
Excitation trouble- excitation
transformer temperature high, failure of power supply to grid control or manual regulator.
12.
Generator seal oil level in damper tank
decreases to “Emergency Level”.
13.
Steam temperature before ESV drops down
to 4500 C.
14.
Boiler master fuel trip.
B.
Tripping of 86G-3 will result in the
following operations :-
86G-3 will trip out the turbine
lock out relay which in turn trip 86G-1 through low forward power relay when
ESV and IV are closed.
Comments
Post a Comment